Single stool elements are used as filters (for the efficient and continuous removal of solids such as rust, sand and other particulates) or as filter water separators (for removal of water from aviation fuels, hydrocarbons and other industrial fluids). Single stool elements are uniquely designed for applications at dispenser, carts and fueling cabinets.
Application Area
- Aviation Fuels: Jet Fuel, AVGAS
- Industrial Fuels: Diesel, Biodiesel, Fuel Oil, Gasoline
- Oils & Lubricants: Lubricating, Hydraulic, Synthetic, Turbine Lube, Compressor Lube
- Water Based Fluids: Cutting Fluids, Coolants
Standard Design
- Filtration Rating:
- Filters – 1, 5, 10 & 25 um
- Coalescers – 1 um
- Seal:
- All seals Buna-N unless otherwise specified
- Center tube:
- Filters – corrosion resistance plated steel
- Coalescer/Separator – epoxy coated steel
- Flow direction:
- Outside-to-in
- Change-out differential pressure:
- 25 psi/172 kPa for Filters
- 15 psi/150 kPa for Coalescer/Separator
- Maximum pressure differential rating:
- 70 psi/482 kPa
- Filter service life (max):
- 36 months (1)
- Storage life (max):
- 60 months (2)
- Filter operating temperature:
- Aviation: Min. -10 °C (14 °F)/Max. 50 °C (122 °F),
- Industrial: -29 °C (-20 °F)/Max. 121 °C (250 °F)
1) Manufacturer recommendation
2) Manufacturer recommendation: 20 °C(68 °F)and max. 50% humidity after date of shipment of out of stock of FAUDI Aviation Americas
Applications
Filters
A single stage element to remove fine solid particulates from the process fluid. When contaminated fluid enters the vessel, fine solids are removed, providing clarification of fluid downstream. The filter for aviation are qualified to Energy Institute specification EI1590 3rd Edition.
Coalescer/Separator Elements
The coalescer/separator system consists of two stages in one to separate water from fuel. A coalescer/separator element is to be used to separate free water and filter fine solids, like rust, dirt and other contaminants from incoming fluids. For aviation fuel, the system is qualified to Energy Institute specification EI1581 6th Edition.
Quality Replacements for:
-
Filtration Group (Facet)
- Parker Hannifin (Velcon, Racor)